Products / Protection Relay

REM615 / REM601

ABB Relion REM Series Motor Protection Relay

REM615 / REM601
ABBProtection Relay

When MV motor protection is needed — including thermal overload, locked rotor, starts per hour, unbalance and RTD temperature monitoring — the ABB REM series is what we specify. REM601 covers essential motor protection at low cost, while REM615 adds directional earth fault, IEC 61850 Ethernet communication and machine differential protection for larger or more critical motors.

IEC 60255-1IEC 61850 Ed.1/Ed.2IEC 60870-5-103Modbus RTU

About this product

The ABB REM series provides MV motor protection covering the full range from essential overcurrent-based functions to advanced differential protection for large critical machines. REM601 is the entry-level model providing time-overcurrent, earth fault, thermal overload (49RMS), locked rotor (51LR), starts per hour (66), negative sequence (46) and undercurrent (37) protection with RS485 communication — the complete set of functions required for the majority of MV motor applications at minimum cost. REM615 adds directional earth fault (67/67N), IEC 61850 Ethernet communication, up to 6 RTD temperature inputs and machine differential protection for larger motors where internal fault detection is required. REM615 is available in four hardware configurations: E (standard IEC), G (global UL/CE), H (high-density I/O) and a motor differential variant. All variants are engineered via PCM600 for consistent parameterisation, testing and post-fault analysis. The relay records start current profiles, thermal state images and disturbance records, enabling both protection coordination verification and predictive maintenance planning. Typical applications include MV motors in pumping stations, compressor drives, fans and industrial process drives. The combination of REM601 for standard applications and REM615 for critical or large motors provides a cost-effective single-vendor approach across mixed motor protection projects in industrial and utility power systems.

Technical Specifications

toolPCM600
modelsREM601 / REM615
rtd inputsup to 6
applicationMV motor protection
communicationRS485 + Ethernet IEC 61850 (REM615)
ansi functions50/51/50N/51N/46/49RMS/48/51LR/66/37/27/59/81/50BF/87M (model dependent)
machine differentialREM615

Ordering Options

Article CodeDescriptionNotes
REM601Essential motor protection, RS485 only
REM615 EStandard IEC 61850 motor relay
REM615 GGlobal certifications (UL/CE) variant
REM615 HHigh-density I/O variant

Request a Consultation

Send us your project requirements and we will get back to you.