ABB Relion REX615 multiapplication protection and control relay
ABBProtection Relay

When one modular relay must cover changing feeder, transformer, line, motor, generator, busbar, capacitor and voltage applications, ABB REX615 combines selectable application packages on one scalable platform.

IEC 60255-1IEC 61850 Edition 1/Edition 2.1IEC 60870-5-103IEC 60870-5-104ModbusDNP3

About this product

ABB Relion REX615 is a freely configurable, all-in-one protection and control relay for power generation and distribution applications. It combines modular hardware with selectable software packages so the same platform can be adapted to feeder, transformer, line, machine, generator, busbar, capacitor bank, voltage and interconnection duties.

Application coverage

REX615 can be configured for:

  • Feeder protection and bay control
  • Transformer protection
  • Line distance and line differential protection
  • Motor and generator protection
  • Busbar and capacitor-bank protection
  • Voltage protection and load shedding
  • Grid automation, Petersen coil control, and auto-synchronization
  • Interconnection and arc protection

ABB divides this functionality into base functions, 12 selectable application packages, and two alternative machine-protection add-on packages: current protection, voltage protection, fault location, feeder extensions, earth-fault extensions, line differential protection, shunt capacitor protection, interconnection protection, machine protection, power transformer protection, busbar protection, on-load tap-changer control, and line distance protection. The package set must be selected against the actual single-line diagram, instrument-transformer arrangement, switchgear control scope, and communication architecture.

Modular hardware and two sizes

REX615 is available in standard and wide sizes. ABB states that the standard size is mechanically aligned with the 615 Series and the wide size with the 620 Series. Hardware dimensions, modules, wiring connections and mounting kits are designed to support modernization and one-to-one replacement planning. The standard version includes four configurable function buttons, while the wide version includes sixteen.

Protection, control and arc detection

The available protection functions depend on the selected application packages. The platform can cover phase overcurrent protection (50/51), earth-fault protection (50N/51N), directional overcurrent protection (67), directional earth-fault protection (67N), line differential protection (87L), distance protection (21), transformer differential protection (87T), machine differential protection (87M/87G), thermal overload protection (49), motor start-up supervision (48/66), breaker failure protection (50BF), auto-reclosing (79), synchrocheck (25), voltage and frequency protection (27/59/81), load shedding and application-specific functions.

Integrated arc detection can supervise the busbar, circuit-breaker and cable compartments. The final sensor count, high-speed output arrangement and trip logic must be verified from the selected hardware and application configuration.

Communication and engineering

REX615 is configured with ABB PCM600. Depending on the communication module, it can support IEC 61850, IEC 60870-5-103, IEC 60870-5-104, Modbus and DNP3. IEC 61850-based station-bus, GOOSE and process-bus functions are configuration dependent. Cybersecurity, user access and network design must be included in the project engineering rather than treated as default settings.

Modernization from 615 and 620 Series

ABB identifies REX615 as the next step for the 615 and 620 Series and states that no further releases are planned for those earlier series. REX615 should therefore be the first comparison point for new specifications, panel extensions and lifecycle modernization. Existing configurations cannot be assumed to migrate automatically; protection functions, logic, I/O, communication, mounting and wiring must be checked application by application.

Technical Specifications

ApplicationsFeeder, transformer, line differential, line distance, motor, generator, busbar, capacitor bank, voltage, interconnection and arc protection
PlatformFully modular and scalable all-in-one relay in standard and wide sizes
CommunicationIEC 61850, IEC 60870-5-103, IEC 60870-5-104, Modbus and DNP3 depending on module
IEC 61850Edition 1 and Edition 2.1; GOOSE and process-bus functions depending on configuration
Sensor SupportConventional instrument transformer and sensor interfaces depending on hardware modules
Arc-Flash ProtectionIntegrated three-compartment arc protection capability
MountingWithdrawable plug-in unit; mechanically aligned with 615 standard and 620 wide sizes
Engineering SoftwareABB PCM600
Product StatusCurrent successor platform for Relion 615 and 620 Series

Application Packages

PackageMain taskTypical useSelection note
APP1Overcurrent protectionBasic feeder, cable and distribution transformer backup protectionConsidered the starting package for basic overcurrent and earth-fault coverage in most REX615 applications
APP2Earth-fault protection extensionAdvanced earth-fault methods for compensated, isolated or high-resistance earthed networksShould be selected after determining the network's neutral arrangement, measured zero-sequence quantities and the directional method
APP3Feeder protection extensionDirectional feeder protection, advanced current elements and power-based protectionsShould be evaluated together with APP1 in ring, meshed or distributed-generation networks
APP4Fault locationEstimated location of short-circuit or earth faults on overhead-line and cable feedersLine parameters, instrument transformers and network earthing data must be entered correctly
APP5Voltage and frequency protectionComprehensive voltage and frequency supervision at busbars, feeders or connection pointsVoltage input hardware and connection method should be determined at the start of the project
APP6Line differential protectionFast and selective zone protection for two-terminal cable or overhead-line sectionsREX615 hardware at both ends, CT ratios and the protection communication channel must be designed together
APP7Shunt capacitor protectionOverload and unbalance protection for single or double-star capacitor banksCapacitor connection type, current and voltage measurement points, and fuse arrangement must be verified
APP8Grid connection protectionSupervision of interconnection conditions for distributed generation, microgrids and grid connection pointsShould be based on the applicable grid code, low-voltage ride-through requirements and active/reactive power limits
APP9Machine protectionThermal model, starting, locked-rotor, load-loss and unbalance protection for asynchronous motorsMotor data, starting time, load characteristics and breaker or contactor control should be evaluated together
ADD1Synchronous machine add-on packageExcitation, stator earth-fault and stability protections for generators and synchronous motorsShould be selected alongside APP9 or related generation/interconnection packages, based on the machine's earthing and excitation system
ADD2Machine differential add-on packageDifferential main protection for the stator winding of a motor or generatorCT arrangement and ratios on both sides, neutral-point access and machine rated values must be verified
APP10Power transformer protectionDifferential main protection, restricted earth fault and backup protection for a two-winding power transformerCT ratios, transformer vector group, earthing and voltage inputs must be defined together
APP11Busbar protectionDifferential zone protection for medium-voltage busbar sectionsBusbar topology, number of feeders, CT connections, trip matrix and breaker-failure logic must be designed together
APP12On-load tap-changer controlAutomatic voltage regulation and OLTC command for a power transformerVoltage measurement, tap position, parallel transformer operating method and command interlocks must be defined
APP13Line distance protectionFive-zone phase and earth distance protection for medium-voltage lines, with communication-assisted tripping schemesLine impedance, zero-sequence compensation, measurement polarity, power swing and the communication scheme must be engineered together

Protection Functions

PackageProtection scopeMain functions
APP1Phase and earth fault, thermal loading and breaker backup protection50/51, 50N/51N, 46, 49F, 50BF
APP2Sensitive and directional earth-fault protection67N, 51N, 59N, 32N
APP3Advanced and directional feeder protection67, 67Q, 51V, 32R/32O
APP4Location analysis of feeder faults and operational supportShort-circuit fault location; earth-fault location; fault analysis through event and disturbance records
APP5Undervoltage, overvoltage, frequency and voltage-sequence component protection27, 59, 81, 59N
APP6Two-terminal line differential main protection and communication-assisted backup protection87L, 67Q, 50BF, 85
APP7Capacitor bank overload, undercurrent and unbalance protection51/37/86C, 60N/60P, 55ITHD, 59NU, 87V
APP8Connection-point voltage, power and islanding protection27RT, 78VS, 32Q/27, 32R/32O
APP9Protection of the asynchronous motor against electrical, thermal and mechanical stresses49M, 46M, 37, 50TDJAM, 48/66/50TDLR
ADD1Synchronous machine and generator-specific protections40, 64TN, 24, 78PS, 21G
ADD2Motor or generator differential main protection87M/87G, 87, 49R (application dependent)
APP10Power transformer main and backup protection87T, 87N, 24, 49T, 51V
APP11Busbar differential main protection and zone tripping logic87B, 87A/87B/87C, 50BF
APP12Transformer voltage regulation, tap-raise and tap-lower control90, 27/59, command interlocks
APP13Phase and earth distance main or backup protection, power swing and protection signaling21P/21N, 21LAL, 68, 78PS, 85

Ordering Options

Article CodeMain ApplicationProtection ScopeProtection Functionsselection differentiatorselection noteNotes
APP1Overcurrent protectionPhase and earth fault, thermal loading and breaker backup protection50/51, 50N/51N, 46, 49F, 50BFBasic feeder, cable and distribution transformer backup protectionConsidered the starting package for basic overcurrent and earth-fault coverage in most REX615 applicationsThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP2Earth-fault protection extensionSensitive and directional earth-fault protection67N, 51N, 59N, 32NAdvanced earth-fault methods for compensated, isolated or high-resistance earthed networksShould be selected after determining the network's neutral arrangement, measured zero-sequence quantities and the directional methodThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP3Feeder protection extensionAdvanced and directional feeder protection67, 67Q, 51V, 32R/32ODirectional feeder protection, advanced current elements and power-based protectionsShould be evaluated together with APP1 in ring, meshed or distributed-generation networksThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP4Fault locationLocation analysis of feeder faults and operational supportShort-circuit fault location; earth-fault location; fault analysis through event and disturbance recordsEstimated location of short-circuit or earth faults on overhead-line and cable feedersLine parameters, instrument transformers and network earthing data must be entered correctlyThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP5Voltage and frequency protectionUndervoltage, overvoltage, frequency and voltage-sequence component protection27, 59, 81, 59NComprehensive voltage and frequency supervision at busbars, feeders or connection pointsVoltage input hardware and connection method should be determined at the start of the projectThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP6Line differential protectionTwo-terminal line differential main protection and communication-assisted backup protection87L, 67Q, 50BF, 85Fast and selective zone protection for two-terminal cable or overhead-line sectionsREX615 hardware at both ends, CT ratios and the protection communication channel must be designed togetherThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP7Shunt capacitor protectionCapacitor bank overload, undercurrent and unbalance protection51/37/86C, 60N/60P, 55ITHD, 59NU, 87VOverload and unbalance protection for single or double-star capacitor banksCapacitor connection type, current and voltage measurement points, and fuse arrangement must be verifiedThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP8Grid connection protectionConnection-point voltage, power and islanding protection27RT, 78VS, 32Q/27, 32R/32OSupervision of interconnection conditions for distributed generation, microgrids and grid connection pointsShould be based on the applicable grid code, low-voltage ride-through requirements and active/reactive power limitsThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP9Machine protectionProtection of the asynchronous motor against electrical, thermal and mechanical stresses49M, 46M, 37, 50TDJAM, 48/66/50TDLRThermal model, starting, locked-rotor, load-loss and unbalance protection for asynchronous motorsMotor data, starting time, load characteristics and breaker or contactor control should be evaluated togetherThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
ADD1Synchronous machine add-on packageSynchronous machine and generator-specific protections40, 64TN, 24, 78PS, 21GExcitation, stator earth-fault and stability protections for generators and synchronous motorsShould be selected alongside APP9 or related generation/interconnection packages, based on the machine's earthing and excitation systemThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
ADD2Machine differential add-on packageMotor or generator differential main protection87M/87G, 87, 49R (application dependent)Differential main protection for the stator winding of a motor or generatorCT arrangement and ratios on both sides, neutral-point access and machine rated values must be verifiedThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP10Power transformer protectionPower transformer main and backup protection87T, 87N, 24, 49T, 51VDifferential main protection, restricted earth fault and backup protection for a two-winding power transformerCT ratios, transformer vector group, earthing and voltage inputs must be defined togetherThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP11Busbar protectionBusbar differential main protection and zone tripping logic87B, 87A/87B/87C, 50BFDifferential zone protection for medium-voltage busbar sectionsBusbar topology, number of feeders, CT connections, trip matrix and breaker-failure logic must be designed togetherThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP12On-load tap-changer controlTransformer voltage regulation, tap-raise and tap-lower control90, 27/59, command interlocksAutomatic voltage regulation and OLTC command for a power transformerVoltage measurement, tap position, parallel transformer operating method and command interlocks must be definedThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.
APP13Line distance protectionPhase and earth distance main or backup protection, power swing and protection signaling21P/21N, 21LAL, 68, 78PS, 85Five-zone phase and earth distance protection for medium-voltage lines, with communication-assisted tripping schemesLine impedance, zero-sequence compensation, measurement polarity, power swing and the communication scheme must be engineered togetherThis code identifies a REX615 application or add-on package, not a standalone relay model and not a complete ABB commercial ordering code. The final relay requires a compatible Standard or Wide REX615 hardware configuration plus any other selected packages.