When an asymmetric elbow/T-type separable connector is needed across a wide current range (630 A up to 1250 A) for polymeric or XLPE-insulated MV cables up to 42 kV, the NKT CB Series is what we specify. Five models cover 25 mm² up to 1200 mm² conductors, with both onshore and offshore variants available.

EN 50180EN 50181HD 629.1 S2

About this product

The NKT CB Series are asymmetric elbow-branch / T-type screened separable connectors used to terminate polymeric or XLPE-insulated medium-voltage cables onto Interface C bushings (per EN 50180 / EN 50181) in switchgear, transformers, and other MV equipment rated up to 42 kV. Unlike a single family-wide current rating, each CB model carries its own continuous current rating: 630 A on CB 24-630 and CB 36-630, and 1250 A on CB 24-1250/2, CB 36-630 (1250), and CB 42-1250/3. Note that a model's compatibility with a C2-class (1250 A) bushing does not raise its own continuous current rating: CB 24-630 and CB 36-630 are both rated 630 A regardless of which bushing class they're paired with. Conductor cross-section ranges from 25 mm² on the smallest model (CB 24-630) up to 1200 mm² on the largest (CB 42-1250/3), with cable insulation diameters spanning 12.7–57.8 mm across the range. The body uses silicone rubber rather than EPDM, and accepts either screwed/shear-head mechanical lugs or hexagonal compression lugs depending on variant. All models include a capacitive voltage measurement point and support cable outer-sheath testing without removing the connector. Depending on model, the range covers both onshore and offshore installation environments.

Technical Specifications

connector geometryAsymmetric elbow branch / T-type screened connector
bushing interfaceEN 50180 / EN 50181, Interface C1 and C2
max system voltage42 kV
Rated Continuous Current630 A or 1250 A, depending on model
conductor cross section25–1200 mm², depending on model, voltage, and conductor construction
cable insulation diameter12.7–57.8 mm
conductor materialAluminium or copper
compatible cable typePolymeric/XLPE-insulated single- or three-core MV cables; EPR on some models
Insulation MaterialSilicone rubber
conductor connection methodScrewed/shear-head mechanical lug or hexagonal compression lug
test measurement featuresCapacitive voltage measurement point and cable outer-sheath test without removing the connector
LPVT / Sensor IntegrationCompatible with dedicated rear-port voltage sensors or LPVT solutions, subject to connector model and interface verification
installation environmentIndoor and outdoor; onshore and offshore applications depending on model

Ordering Options

Article CodeSystem Voltage (kV)Continuous Current (A)Insulation Diameter (mm)Conductor Cross-Section (mm²)Notes
CB 24-63024 kV630 A12.7–34.6 mm25–300 mm²
CB 24-1250/224 kV1250 A21.2–40.0 mm95–500 mm²
CB 36-63042 kV630 A17.0–44.0 mm25–400 mm²
CB 36-630 (1250)42 kV1250 A28.9–51.0 mm150–800 mm²
CB 42-1250/342 kV1250 A21.2–57.8 mm50–1200 mm²