Products / Capacitive Voltage Indicator

CDS Series

Orion EE CDS Series LED Capacitive Voltage Indicators

Orion EE CDS Series LED capacitive voltage indicator for medium voltage switchgear
Orion EECapacitive Voltage Indicator

When compact LED voltage presence indication is needed in MV switchgear, we specify the CDS Series. CDS covers simple local indication, while CDS-R adds a change-over contact for operation-safe signalling, SCADA input or external lamp applications.

IEC 61243-5IEC 62271-213:2021

About this product

Selecting the CDS Series model

The CDS Series is the LED-based CVI family for IEC 62271-213:2021 compliant voltage presence and absence indication. Use CDS when simple local LED indication is enough. Use CDS-R when the same indication must also provide a relay contact for signalling, interlocking or SCADA.

RFQ information

The CDS family still needs the same system-matching information as other CVI units. Please provide the C1 coupling electrode capacitance, cable type and length, cable unit capacitance and nominal voltage Un before quotation.

Model Selection

ModelPositioningDisplayRelay / Contact OutputAuxiliary Power SupplyUse when
CDSCompact LED voltage indicator3-phase flashing LED indicationNot applicableNot applicable for voltage detectionSimple LED-based local voltage presence indication is required
CDS-RLED voltage indicator with status contact3-phase flashing LED indication1 change-over contact24-230 V AC/DCLED indication must also provide a relay contact signal for SCADA, external lamp or interlocking

Model-Based Technical Comparison

ModelDisplayLRM InterfaceRelay / Contact OutputAuxiliary Power SupplyPower ConsumptionContact RatingPower Supply LEDVariable C2 ModuleAMP ConnectionProtection ClassConnection LeadsCutout SizeWeight
CDS3-phase flashing LED indicationLRMNot applicableNot applicable for voltage detectionNot applicableNot applicableNot applicableNoNoIK07 / IP54 (Front)4.8 x 0.8 mm faston terminal92 x 45 mm75 g
CDS-R3-phase flashing LED indicationLRM1 change-over contact24-230 V AC/DCLess than 2 W5 A 250 VAC or 5 A 30 VDC with resistive load1 LED indicator for power supplyOptional2x AMP optionalIK07 / IP54 (Front)4.8 x 0.8 mm faston terminal92 x 45 mm155 g max.

Mechanical Dimensions

ModelFront SizePanel CutoutInstallation DepthBody TypeWeight
CDS95 x 48 mm92 x 45 mm23.35 mmCompact body75 g
CDS-R95 x 48 mm92 x 45 mm63.5 mm max.Relay-output body155 g max.

Common Technical Specifications

ParameterValue
Applicable StandardIEC 62271-213:2021
InterfaceLRM
ApplicationVoltage presence and absence indication in MV equipment
Display Type3-phase flashing LED indication

Relay / Contact Logic

Model / RelayTerminalsAuxiliary PowerVoltage Absent StateVoltage Present State
Relay 15 = NO, 4 = COM, 3 = NC, 2 = +Vaux, 1 = -VauxContacts require auxiliary power to operate.All phases < 10% UnAt least one phase > 45% Un

Type A / Type B Contact Modes

ModeDefinitionSafe Operation Note
Type AStandard contact mode. With auxiliary power present, the contact follows the voltage-absent and voltage-present thresholds.If auxiliary power is lost, the contact cannot actively signal the voltage-present safe position.
Type BOperation-safe contact mode. If auxiliary power is lost, the contact takes the voltage-present position.This prevents unsafe operation by treating loss of auxiliary power as a live-voltage condition.

Required Data for Order

Required Data for Order
Capacitance of coupling electrode C1
Cable type, length and unit capacitance
Nominal voltage Un

C2 Capacitance Options

C2 Capacitance Options
1, 1.2, 1.5, 1.8, 2.2, 2.7, 3.3, 3.9 nF
4.7, 5.6, 6.8, 8.2, 10, 12, 15, 18, 22 nF
27, 33, 39, 47, 56, 68, 82, 100 nF

Related Solution

Voltage Detection & Indication Systems

Explore the solution →

Request a Consultation