Products / Protection Relay

PowerLogic P3F

PowerLogic P3F Feeder Protection Relay

PowerLogic P3F
Schneider ElectricProtection Relay

When MV feeder protection requires advanced functions — including directional earth fault, arc flash detection, LPCT/LPVT sensor inputs and IEC 61850 Ethernet communication — the P3F is what we specify. It covers all standard feeder ANSI functions and supports built-in virtual injection testing to reduce commissioning time.

IEC 60255-1IEC 61850 Ed.1/Ed.2IEC 60870-5-103ModbusDNP3

About this product

The Schneider Electric P3F is an advanced MV feeder protection relay covering the complete set of functions required for directional feeder protection in utility distribution and industrial power systems with IEC 61850 substation automation. Beyond the core overcurrent and earth fault functions, the P3F adds directional phase overcurrent (67) and earth fault (67N) for meshed and multi-source networks, arc flash detection via optional external light point sensors, active and reactive power measurement (32), thermal overload protection (49), LPCT/LPVT low-power sensor compatibility and full IEC 61850 Edition 1 and Edition 2 Ethernet communication with DNP3 and Modbus as alternatives. A built-in virtual injection test capability allows protection settings to be verified by simulating test currents and voltages internally without requiring a secondary injection test set, significantly reducing commissioning time on projects with large numbers of similar protection relays. IEC 62443 cybersecurity standards are supported with role-based access control and secure communication, meeting the requirements of utility and critical infrastructure projects. Typical applications include MV feeder bay protection in DSO distribution substations with IEC 61850 automation systems, industrial primary switchgear feeders in oil and gas, petrochemical and heavy industry where directional earth fault and IEC 61850 GOOSE inter-tripping are required, renewable energy substation feeder protection, and retrofit of existing switchgear where Ethernet-based SCADA integration is being introduced alongside relay replacement.

Technical Specifications

mountingflush-mount
arc flashoptional light point sensors
ip ratingIP54
applicationMV feeder protection
communicationRS485 + Ethernet (IEC 61850 Ed.1/Ed.2 / Modbus / DNP3)
cybersecurityIEC 62443
ansi functions50/51/50N/51N/67/67N/79/27/59/81/32/46/49/50BF
current inputs3x CT or LPCT + earth CT
supply voltage24-250V DC / 100-230V AC
voltage inputs4x VT or LPVT

Ordering Options

Article CodeDescriptionNotes
P3F30 CT/VTStandard conventional CT/VT inputs
P3F30 LPCT/LPVTLow power sensor (LPCT/LPVT) inputs