Products / Protection Relay

PowerLogic P5x20

PowerLogic P5x20 Protection Relay

PowerLogic P5x20
Schneider ElectricProtection Relay

When a demanding MV application requires LPCT/LPVT sensor support, IEC 61850 Ethernet communication and a compact non-withdrawable form factor — the P5x20 is what we specify. It covers universal feeder and voltage protection with the same modular communication architecture as the P5x30 but without arc flash detection.

IEC 60255-1IEC 61850 Ed.1/Ed.2IEC 62443 SL1IEC 60870-5-103DNP3Modbus

About this product

The Schneider Electric P5x20 is a compact non-withdrawable MV protection relay from the EasyLogic P5 platform, designed for demanding applications requiring LPCT/LPVT low-power sensor compatibility and IEC 61850 Ethernet communication in a smaller form factor than the withdrawable P5x30. Three variants cover feeder/motor universal (P5U20 CT), LPCT/LPVT sensor input universal (P5U20 LPCT/LPVT) and voltage-only (P5V20) applications, with up to 16 digital inputs and 8 relay outputs for applications requiring moderate I/O. The relay supports eight simultaneous communication protocols including IEC 61850 Ed.1 and Ed.2, Modbus RTU and TCP, DNP3, IEC 60870-5-103/104 and GOOSE peer-to-peer communication, with IEC 62443 SL1 cybersecurity certification for utility and critical infrastructure applications. The non-withdrawable design is appropriate for installations where the reduced footprint of the P5x20 compared to the P5x30 provides a panel design advantage. Typical applications include MV protection in compact switchgear designs using LPCT/LPVT sensors instead of conventional instrument transformers, feeder and motor protection requiring IEC 61850 communication with eight protocol support in a cost-optimised platform, and utility and industrial MV protection projects where arc flash detection and dual redundant Ethernet are not required but LPCT sensor compatibility and full protocol support are.

Technical Specifications

designnon-withdrawable
arc flashfalse
lpct lpvtyes (IEC 61869-10/11)
applicationuniversal feeder and voltage — compact MV
communicationRS485 + Ethernet (IEC 61850 Ed.1/Ed.2 / Modbus / DNP3 / 8 protocols)
cybersecurityIEC 62443 SL1
digital inputsup to 16
supply voltage24-250V DC / 100-230V AC
digital outputsup to 8

Ordering Options

Article CodeDescriptionNotes
P5U20 CTUniversal — conventional CT/VT inputs
P5U20 LPCT/LPVTUniversal — low power sensor inputs
P5V20Voltage protection only

Request a Consultation

Send us your project requirements and we will get back to you.