PowerLogic P3 Series

PowerLogic P3 Series MV Protection Relays

Schneider Electric PowerLogic P3 Series protection relay
Schneider ElectricProtection Relay

When standard or advanced MV protection is needed across feeder, motor, generator, or transformer applications, the PowerLogic P3 Series is what we specify. P3 Standard (P3U20, P3U30) covers essential to directional feeder and motor protection, while P3 Advanced adds dedicated models for line differential (P3L30), motor differential (P3M32), generator (P3G30/P3G32), and transformer differential (P3T32) protection, all with IEC 61850 Edition 1/Edition 2 and optional LPCT/LPVT sensor support.

IEC 60255-1IEC 61850 Ed.1/Ed.2IEC 60870-5-103ModbusDNP3

About this product

PowerLogic P3 Series combines protection, measurement, control, and communication for MV distribution systems. The current official range is not limited to the broad P3F, P3M, and P3U labels; it contains nine application-specific models across the P3 Standard and P3 Advanced platforms.

Platform structure

  • P3 Standard: Includes the P3U20 and P3U30 universal models.
  • P3 Advanced: Includes the P3F30, P3L30, P3M30, P3M32, P3G30, P3G32, and P3T32 application models.

P3U20 is intended for essential feeder and motor applications, while P3U30 adds directional, voltage, and frequency capabilities for a wider application scope. P3 Advanced provides separate model codes for feeder, line differential, motor, generator, and transformer differential applications.

Model selection

P3F30 is used for directional feeder and incomer protection, P3L30 for line or cable differential protection, P3M30 for motor protection, and P3M32 for motor differential protection. P3G30 is intended for generator protection, P3G32 for generator differential protection, and P3T32 for transformer differential protection.

LPCT and LPVT support is available only on selected models. Arc-flash detection can be implemented on the P3 Advanced platform. IEC 61850 Edition 1 and Edition 2 support, together with serial and Ethernet communication options, simplifies system integration.

Engineering and operation

eSetup Easergy Pro is used for settings, configuration, commissioning, and fault analysis. Built-in virtual injection testing, IEC 61850 GOOSE, and extended I/O are available depending on the selected model and hardware configuration.

Typical applications

  • Utility feeder bays
  • Industrial MV switchboards
  • Pump, compressor, and large motor applications
  • Distribution and power transformers
  • Generator and cogeneration plants
  • Line and cable differential protection
  • IEC 61850 modernization projects

Technical Specifications

ApplicationsFeeder, motor, transformer, generator, and line differential protection
PlatformP3 Standard and P3 Advanced
CommunicationSerial and Ethernet; multiple protocols depending on configuration
IEC 61850Available, Edition 1 and Edition 2
Sensor SupportConventional CT/VT; LPCT/LPVT on selected models
Arc-Flash ProtectionAvailable on P3 Advanced
MountingFlush-mounted Standard and Advanced cases
Engineering SoftwareeSetup Easergy Pro
Product StatusCurrent

Model Selection

ModelPlatformMain applicationDistinguishing protectionWhen should it be selected?
P3U20P3 StandardUniversal feeder and motor protectionBasic current-based feeder and motor protectionWhen voltage-based directional functions are not required
P3U30P3 StandardUniversal feeder, motor, and transformer protectionDirectional current, voltage and frequencyWhen broader application coverage is required from one universal model
P3F30P3 AdvancedDirectional feeder and incomer protectionDirectional feeder protection, autoreclosing and arc flashWhen advanced feeder automation and IEC 61850 are required
P3L30P3 AdvancedLine and cable differential protectionLine differential protection (87L)When fast selective protection is required for a two-ended line or cable section
P3M30P3 AdvancedMotor protectionThermal, starting and locked-rotor protectionFor standard protection of large and critical motors
P3M32P3 Advanced differentialMotor differential protectionMotor differential protection (87M)When currents from both sides of the motor are to be compared
P3G30P3 AdvancedGenerator protectionPower, excitation and pole-slip protectionWhen generator-specific protection is required
P3G32P3 Advanced differentialGenerator differential protectionGenerator differential protection (87G)When generator differential protection is required
P3T32P3 Advanced differentialTransformer differential protectionTransformer differential protection (87T)For power-transformer differential protection

Hardware and Integration

ModelMeasurement inputsDigital I/OSensor supportIEC 61850Special hardware or integration
P3U203 conventional CT inputs, residual-current input, and 1 VT input8 or 10 digital inputs; 5 or 8 outputs plus self-supervisionConventional CT/VTAvailable, Ed.1 and Ed.2Up to 12 temperature inputs with optional modules; built-in virtual injection testing
P3U303 CT or LPCT inputs, residual-current input, and 4 VT or LPVT inputs14 or 16 digital inputs; 8 or 11 outputs plus self-supervisionConventional CT/VT or LPCT/LPVTAvailable, Ed.1 and Ed.2Power and energy measurements; built-in virtual injection testing
P3F303 CT or LPCT inputs, residual-current input, and 4 VT or LPVT inputs6 to 36 digital inputs; 10 to 21 outputs plus self-supervisionConventional CT/VT or LPCT/LPVTAvailable, Ed.1 and Ed.2Arc-flash sensors, IEC 61850 GOOSE, directional protection, fault location, and virtual injection testing
P3L303 conventional CT inputs, residual-current input, and 4 conventional VT inputs6 to 36 digital inputs; 10 to 21 outputs plus self-supervisionConventional CT/VTAvailable, Ed.1 and Ed.2Two line differential stages; dedicated line differential communication interface
P3M303 CT or LPCT inputs, residual-current input, and 4 VT or LPVT inputs6 to 36 digital inputs; 10 to 21 outputs plus self-supervisionConventional CT/VT or LPCT/LPVTAvailable, Ed.1 and Ed.2Temperature monitoring with optional RTD modules; motor starting supervision
P3M326 conventional CT inputs, residual-current inputs, and 4 conventional VT inputs6 to 16 digital inputs; 10 to 13 outputs plus self-supervisionConventional CT/VTAvailable, Ed.1 and Ed.2Motor differential protection and optional temperature monitoring
P3G303 conventional CT inputs, residual-current input, and 4 conventional VT inputs6 to 36 digital inputs; 10 to 21 outputs plus self-supervisionConventional CT/VTAvailable, Ed.1 and Ed.2Generator-specific power and excitation protection functions
P3G326 conventional CT inputs, residual-current inputs, and 4 conventional VT inputs6 to 16 digital inputs; 10 to 13 outputs plus self-supervisionConventional CT/VTAvailable, Ed.1 and Ed.2Generator differential and low-impedance restricted earth fault protection
P3T326 conventional CT inputs, residual-current inputs, and 4 conventional VT inputs6 to 16 digital inputs; 10 to 13 outputs plus self-supervisionConventional CT/VTAvailable, Ed.1 and Ed.2Transformer differential protection with vector group and ratio compensation

Protection Functions

ModelProtection scopeMain functions
P3U20Essential feeder and motor protection with current-based measurement37, 46, 46BC, 48/51LR, 49, 50/51, 50N/51N, 50BF, 64REF, 67N, 86 (application dependent)
P3U30Directional current, voltage, frequency, feeder, motor, and transformer-related protection27, 37, 46, 48/51LR, 49, 50/51, 50N/51N, 50BF, 59, 59N, 64REF, 67, 67N, 79, 81, 81R, 86 (application dependent)
P3F30Directional feeder protection, voltage and frequency supervision, auto-reclosing, and arc-flash schemes27, 49, 50/51, 50N/51N, 50BF, 59, 59N, 64REF, 67, 67N, 67NI, 79, 81, 81R, 86, 50ARC
P3L30Line differential protection with feeder backup, voltage supervision, and in-zone transformer support27, 49, 50/51, 50N/51N, 50BF, 59, 64REF, 67, 67N, 81, 81R, 86, 87L, 50ARC
P3M30Thermal, starting, locked-rotor, unbalance, undercurrent, and directional motor protection37, 46, 48/51LR, 49, 50/51, 50N/51N, 50BF, 66, 67, 67N, 81, 86, 50ARC
P3M32Motor differential, thermal, starting, unbalance, and backup overcurrent protection37, 46, 48/51LR, 49, 50/51, 50N/51N, 50BF, 64REF, 66, 67, 67N, 81, 86, 87M, 50ARC
P3G30Generator voltage, frequency, power, loss-of-field, pole-slip, and backup overcurrent protection21G, 24, 25, 27, 32R/32L, 40, 46, 49, 50/51, 50N/51N, 51V, 59, 64S, 67, 67N, 78PS, 81, 81R, 86, 50ARC
P3G32Generator differential protection with generator voltage, frequency, power, and backup functions21G, 24, 25, 27, 32R/32L, 40, 46, 49, 50/51, 50N/51N, 51V, 59, 64REF, 64S, 67, 67N, 78PS, 81, 81R, 86, 87G, 50ARC
P3T32Transformer differential, restricted earth fault, overfluxing, temperature, and backup overcurrent protection24, 26/63, 49, 50/51, 50N/51N, 50BF, 64REF, 67, 67N, 81, 86, 87T, 50ARC

Related Solution

Protection Relays for DSOs

Explore the solution →