Products / Protection Relay

PowerLogic P5 Series

PowerLogic P5 Series Protection and Control Relays

Schneider Electric PowerLogic P5 Series protection and control relay
Schneider ElectricProtection Relay

When demanding MV protection or bay control is needed with a withdrawable, modular platform, the PowerLogic P5 Series is what we specify. The compact P5x20 covers voltage/frequency (P5V20) and universal current-based protection (P5U20, in CT or LPCT/LPVT versions), while the expanded P5x30 adds directional feeder (P5F30), motor (P5M30), transformer differential (P5T30), and line differential (P5L30) models with up to 6 arc-flash point sensors and redundant Ethernet. Both platforms support IEC 61850 and are the current reference platform for Sepam and MiCOM modernization under Schneider's ECOFIT approach.

IEC 60255-1IEC 61850 Ed.1/Ed.2IEC 62443 SL1IEC 60870-5-103DNP3Modbus

About this product

PowerLogic P5 Series is a modular, withdrawable relay platform for demanding MV protection and bay control applications. The current range is divided into two case sizes, but both platforms use a withdrawable design. The previous statement describing P5x20 as fixed-mounted has been removed in line with the official 2026 catalog.

Platform and model structure

  • P5x20: Includes the compact P5V20 and P5U20 models. P5U20 can be selected as a conventional CT version or an LPCT/LPVT version.
  • P5x30: Includes P5F30, P5M30, P5T30, and P5L30. It provides higher I/O capacity and support for up to 6 arc-flash point sensors.

P5V20 is used for voltage and frequency protection, P5U20 for universal protection, P5F30 for directional feeder protection, P5M30 for motor protection, P5T30 for transformer differential protection, and P5L30 for line or cable differential protection.

Reliability and maintenance

The withdrawable design simplifies maintenance and device replacement. Optional backup memory supports automatic restoration of settings and records to a replacement device. Arc-flash detection, redundant Ethernet, and expanded digital I/O on P5x30 improve availability in critical installations.

Communication and condition monitoring

Depending on configuration, PowerLogic P5 supports IEC 61850, serial communication, Ethernet, PRP, HSR, and RSTP. Wireless temperature and environmental condition monitoring can be implemented with PowerLogic TH110 and CL110 sensors.

Retrofit use

P5 is the current platform used in Schneider Electric's ECOFIT approach for modernization of selected Sepam and MiCOM ranges. A direct replacement must not be assumed before verifying the existing relay functions, CT/VT connections, I/O arrangement, communication, and panel dimensions.

Typical applications

  • Utility substations
  • Industrial MV distribution systems
  • Motor, transformer, and line differential protection
  • Data centers and critical infrastructure
  • Oil, gas, mining, and water facilities
  • IEC 61850 and redundant Ethernet projects
  • Sepam and MiCOM modernization applications

Technical Specifications

ApplicationsVoltage, universal, feeder, motor, transformer, and line differential protection
PlatformP5x20 compact and P5x30 expanded withdrawable platforms
CommunicationSerial, Ethernet, redundant Ethernet, and wireless options depending on configuration
IEC 61850Available, Edition 1 and Edition 2
Sensor SupportConventional CT/VT and LPCT/LPVT depending on model
Arc-Flash ProtectionAvailable on P5x30 with up to 6 point sensors
MountingWithdrawable flush-mounted design
Engineering SoftwareeSetup Easergy Pro and EcoStruxure Power Device app
Product StatusCurrent

Model Selection

ModelPlatformMain applicationDistinguishing featureWhen should it be selected?
P5V20P5x20 compactVoltage and frequency protectionVoltage, frequency, neutral-voltage displacement and load sheddingFor independent voltage and frequency protection
P5U20 CTP5x20 compactUniversal current-based protectionConventional CT inputsWhen a compact advanced platform is required with an existing CT infrastructure
P5U20 LPCT/LPVTP5x20 compact sensor versionUniversal directional protection with low-power sensorsLPCT and LPVT inputsIn switchgear using low-power instrument sensors
P5F30P5x30 expandedDirectional feeder and incomer protectionDirectional protection, power quality and arc flashFor critical, communication-intensive or automated feeders
P5M30P5x30 expandedMotor protectionMotor starting, RTD and speed optionsFor large and critical motors
P5T30P5x30 differentialTransformer differential protectionTransformer differential protection (87T)For power-transformer differential protection
P5L30P5x30 expandedLine and cable differential protectionLine differential protection (87L)When fast selective protection is required for line and cable sections

Hardware and Integration

ModelMeasurement inputsDigital I/OSensor supportIEC 61850Special integration
P5V204 conventional VT inputs4 to 16 digital inputs; 3 to 8 outputs plus watchdogConventional VTAvailable depending on communication configurationCompact P5 platform for dedicated voltage and frequency applications
P5U20 CT3 conventional CT inputs and residual-current input4 to 16 digital inputs; 3 to 8 outputs plus watchdogConventional CTAvailable depending on communication configurationUniversal compact platform with external RTD and analogue I/O options
P5U20 LPCT/LPVT3 LPCT inputs, residual-current input, and 4 LPVT inputs4 to 16 digital inputs; 3 to 8 outputs plus watchdogLPCT and LPVTAvailable depending on communication configurationLow-power sensor version of the universal compact platform
P5F303 CT or LPCT inputs, residual-current input, and 4 VT or LPVT inputs4 to 40 digital inputs; 3 to 18 outputs plus watchdogConventional CT/VT or LPCT/LPVTAvailable, Edition 1 and Edition 2Power quality measurements, redundant Ethernet, and optional wireless condition monitoring
P5M303 CT or LPCT inputs, residual-current input, and 4 VT or LPVT inputs4 to 40 digital inputs; 3 to 18 outputs plus watchdogConventional CT/VT or LPCT/LPVTAvailable, Edition 1 and Edition 2Motor starting supervision, optional RTD modules, and optional speed detection
P5T306 conventional CT inputs, 2 residual-current inputs, and 1 VT input4 to 40 digital inputs; 3 to 18 outputs plus watchdogConventional CT/VTAvailable, Edition 1 and Edition 2Transformer differential protection with ratio and vector group compensation
P5L303 CT or LPCT inputs, residual-current input, and 4 VT or LPVT inputs4 to 40 digital inputs; 3 to 18 outputs plus watchdogConventional CT/VT or LPCT/LPVTAvailable, Edition 1 and Edition 2Line differential communication, capacitive charging-current compensation, and redundant Ethernet

Protection Functions

ModelProtection scopeMain functions
P5V20Voltage, frequency, neutral displacement, VT supervision, and load-shedding protection27, 59, 47, 59N, 60FL, 81, 81R, 86
P5U20 CTNon-directional feeder, transformer, motor backup, and general overcurrent protection46, 49, 50/51, 50N/51N, 50BF, 64REF, 86 (application dependent)
P5U20 LPCT/LPVTDirectional current, voltage, frequency, feeder, transformer, and general protection27, 46, 49, 50/51, 50N/51N, 50BF, 59, 59N, 64REF, 67, 67N, 81, 81R, 86 (application dependent)
P5F30Directional feeder protection, voltage and frequency supervision, auto-reclosing, power quality, and arc-flash schemes27, 49, 50/51, 50N/51N, 50BF, 59, 59N, 64REF, 67, 67N, 79, 81, 81R, 86, 50ARC
P5M30Thermal, starting, locked-rotor, unbalance, undercurrent, directional, and arc-flash protection37, 46, 48/51LR, 49, 50/51, 50N/51N, 50BF, 66, 67, 67N, 81, 86, 50ARC
P5T30Transformer differential, restricted earth fault, overfluxing, Buchholz, temperature, and backup overcurrent protection24, 26/63, 49, 50/51, 50N/51N, 50BF, 64REF, 86, 87T, 50ARC
P5L30Line and cable differential protection with feeder backup, voltage supervision, charging-current compensation, and in-zone transformer support27, 49, 50/51, 50N/51N, 50BF, 59, 64REF, 67, 67N, 81, 81R, 86, 87L, 50ARC